UPS Power Up
From athena
Crash course on UPS startup...
The only way to bring the UPS from a gentle shutdown is to restore power
Restoring power to UPS:
- Flip the breaker on main PDU to restore power
- UPS should self boot but not provide output power
- Press "ESC"
- Select "Control" and press enter
- Press down keys to "turn UPS output on" and press enter
- go from Cancel to Yes
- Confirm it...
- The UPS load should come on
- look in rear of Rack 0 for red light on white DC adapter supplying power to the water switch
- head back into 480V PDU and check EPO
- look next to test/armed switch for red tripped LED light
- if it's not lit, switch from TEST back into ARMED
- close the back of the PDU
- Flip the breakers for Rack 1
- head to Polyserve Power Up Procedure